One of the most common parts to fail on a single-phase HVAC system is a run capacitor, so much so that we sometimes refer to junior techs as “capacitor changers.” While capacitors may be easy to diagnose and replace, here are some things many techs may not know.

A capacitor is a device that stores a differential charge on opposing metal plates. While capacitors can be used in circuits that boost voltage, they don’t actually increase voltage themselves. We often see higher voltage across a capacitor than the line voltage, but this is due to the Back EMF (Counter electromotive force) generated by the motor, not the capacitor. 300kw Soft Starter

5 Capacitor Facts You Should Know | 2019-06-10  | ACHR News

Techs notice that the one side of power is connected to the C terminal or the side opposite the run winding. Many techs imagine that this power “feeds” into the terminal, gets boosted or shifted, and then enters the compressor or motor through the other side. While that may make sense, it isn’t actually how a capacitor works.

A typical HVAC run capacitor is just two long sheets of thin metal, insulated with an insulation barrier of very thin plastic and immersed in an oil to help dissipate heat. Just like the primary and secondary of a transformer the two sheets of metal never actually touch, but electrons do gather and discharge with every cycle of the alternating current.  For example, the electrons that gather on the “C” side of the capacitor never go “through” the plastic insulation barrier over to the “Herm” or “Fan” side. The two forces simply attract and release in and out of the capacitor on the same side they entered.

On a properly wired PSC (permanent split capacitor) motor, the only way the start winding can have any current move through is if the capacitor stores and discharges. The higher the MFD of the capacitor, the greater the stored energy and the greater the start winding amperage. If the capacitor is completely failed with zero capacitance, it is the same as having an open start winding. Next time you find a failed run capacitor (with no start capacitor), read the amperage on the start winding with a clamp to see what I mean.

This is why oversizing a capacitor can quickly cause damage to a compressor. By increasing the current on the start winding the compressor start winding will be much more prone to early failure.

Many techs think they must replace a 370v capacitor with a 370v capacitor. The voltage rating displays the “not to exceed” rating, which means you can replace a 370v with a 440v but you cannot replace a 440v with a 370v. This misconception is so common that many capacitor manufactures began stamping 440v capacitors with 370/440v just to eliminate confusion.

You simply measure the current (amps) of the motor start winding coming off of the capacitor and multiply it times 2652 (on 60hz power 3183 on 50hz power) and then divide that number by the voltage you measure across the capacitor. 

Want more HVAC industry news and information? Join The NEWS on Facebook, Twitter, and LinkedIn today!

Bryan Orr is the vice president at Kalos Services Inc. and founder of the HVAC School. 

You must have JavaScript enabled to enjoy a limited number of articles over the next 30 days.

Sponsored Content is a special paid section where industry companies provide high quality, objective, non-commercial content around topics of interest to the ACHR News audience. All Sponsored Content is supplied by the advertising company. Interested in participating in our Sponsored Content section? Contact your local rep.

On Demand In this webinar, we go through the recent updates on R-290 natural refrigerant, and the impact it will have on the HVACR industry.

Copyright ©2023. All Rights Reserved BNP Media.

5 Capacitor Facts You Should Know | 2019-06-10  | ACHR News

Vfd Inverter 7.5kw 380v Design, CMS, Hosting & Web Development :: ePublishing